Methodology
Last updated:
This page documents exactly how our calculators work, so you can check the math and decide how far to trust a result. The values below are read directly from the code and datasets that power the site.
Generator sizing
- Running load = the sum of running watts × quantity for every selected appliance.
- Start-up surge = starting watts − running watts for each motor load. With "one at a time" (default), only the largest single surge is added; with "at the same time", all surges are added.
- Peak = running load + start-up surge.
- Recommended running watts = running load ÷ continuous-load ratio ÷ elevation factor, rounded up to the next 500 W. The default ratio is 80%: the generator is never asked to run above that share of its rating.
- Recommended surge watts = peak ÷ elevation factor, rounded up to the next 500 W.
Assumptions and their sources
| Assumption | Value we use | Why |
|---|---|---|
| Continuous-load headroom | 80% of rating (adjustable) | Common recommendation in generator manuals for long runtimes and motor starts. |
| Soft-starter surge reduction | 60% | Manufacturers commonly claim 60–75%; we use the low end to stay conservative. Applied only to central AC/heat-pump compressors and custom loads. |
| Elevation derating | 3.5% per 1,000 ft | Rule of thumb for naturally aspirated engines. Your engine manual has the exact figure. |
| Starting watts from nameplate | LRA × volts | Upper bound: real inrush lasts milliseconds and is usually lower. Running watts are RLA × volts. |
| Motors starting together | No (adjustable) | Compressors and pumps cycle independently, so simultaneous starts are uncommon. |
Data sources and verification
- Appliances (25 entries): 25 use typical values from published manufacturer wattage charts and are labelled as typical in the calculator. Your own appliance may differ — the nameplate on it is always the better number, and the calculator accepts it.
- Generators (0 verified): ratings per fuel from the manufacturer's specification sheet. A model appears in results only after we have checked its spec sheet and recorded the link and date.
- Batteries (0 verified): capacity and continuous output from manufacturer specifications, under the same rule.
- Fuel prices: U.S. Energy Information Administration (EIA) — weekly retail prices, refreshed weekly by an automated job. EIA publishes residential propane prices only during the heating season and only for surveyed states; outside that window we show the last published value and its date.
What the calculators don't account for
- Power quality: some electronics and variable-speed equipment need an inverter generator's cleaner output.
- Wiring and installation details such as wire length, transfer-switch type and load-management modules.
- Extreme temperatures, worn motors and poorly maintained engines, which all increase demand or reduce output.
- Local codes, permits and utility requirements.
Results are estimates for planning. Have a licensed electrician confirm sizing before installation.
Updates and corrections
Every page shows when it was last updated and when its data was last checked. Datasets are reviewed at least every six months and whenever a reader reports a problem. Corrections that change a result are noted on the affected page. Report an issue through our contact page.